High Limit Aquastat

Description for Honeywell L8124E1016

Description:
Triple Aquastat Relay with High limit : 10F fixed. low limit: 10-25F adj. Differential
Application:
Triple Aquastat Relay with High limit
Operating Range, Low Limit (F): 110F to 220F
Operating Range, Low Limit (C): 43C to 104C
Operating Range, High Limit (F): 130F to 240F
Operating Range, High Limit (C): 54C to 116C
Differential Temperature (F): High limit : 10F fixed. low limit: 10-25F adj.
Switching Action: SPST: High & Low Limit
Maximum Operating Pressure (psi): 200 psi on outside of immersion well, 100 psi on capsule if inserted directly.
Maximum Operating Pressure (kPa): 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.
Electrical Ratings (burner AFL) Line Voltage: 7.4 A @ 120 Vac. 3.7 A @ 240 Vac
Electrical Ratings (burner ALR) Line Voltage: 44.4 A @ 120 Vac. 22.7 A @ 240 Vac Electrical Ratings (circulator AFL): 7.4 A @ 120 Vac. 3.7 A @ 240 Vac
Electrical Ratings (circulator ALR): 44.4 A @ 120 Vac. 22.7 A @ 240 Vac
Voltage: 120 Vac
Frequency: 60 Hz
Dimensions (in.): 6 1/8 in. high x 4 3/8 in. wide x 3 1/16 in. deep
Dimensions (mm): 156 mm high x 111 mm wide x 78 mm deep
Mounting: Vertical Mounting
Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Maximum Ambient Temperature (F): 150F at switches, 265F at sensing element.
Maximum Ambient Temperature (C): 66C at switches, 129C at sensing element.
Minimum Ambient Temperature (F): -30F
Minimum Ambient Temperature (C): -9C
Electrical Connections: Quick-Connect / Screw
Tradeline: Value Tradeline
Ref: Honeywell.com

Categories: ,

Description

Specs

Application: Triple Aquastat Relay
High Limit
Switch Action: SPST
Temperature Range (F): 130°F to 240°F
110°F to 220°F
Electrical Rating: Circulator: 7.4 A @ 120 Vac
Burner: 3.7 A @ 240 Vac
Circulator: 3.7 A @ 240 Vac
Burner: 7.4 A @ 120 Vac
Electrical Ratings (ALR): Circulator: 22.2 A @ 240 Vac
Burner: 22.2 A @ 240 Vac
Burner: 44.4 A @ 120 Vac
Circulator: 44.4 A @ 120 Vac
Max Temp Differential: 10°F
Differential: 10° to 25°F (Low Limit)
Max Temp Differential: 25°F
Min Temp Differential: 10°F
Differential: Adjustable
Fixed
Height: 6-1/8″
Width: 4-3/8″
Depth (Inches): 3-1/16″
Operating Humidity: 0% to 95% (non-condensing)
Max Ambient Temp (°F): 265 F at Sensing Element
150 F at Switches
Mount: Vertical
Voltage: 120v
Frequency: 60 Hz
Max Pressure (PSI): 200 psi on Immersion Well
100 psi Direct Immersion
Connection Type: Quick-Connect